Customization: | Available |
---|---|
Application: | High-voltage |
Material: | Porcelain |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ANSI class | 57-1 | 57-2 | 57-3 | 57-4 | 57-5 | |
Fig no. | 1 | 2 | 3 | 4 | 5 | |
creepage distance-mm | 356 | 559 | 737 | 1015 | 1145 | |
Dry arcing distance-mm | 165 | 241 | 311 | 368 | 438 | |
Mechanical cantilever failing load-KN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | |
Cantilever strength routine test -KN | 5 | 5 | 5 | 5 | 5 | |
Type application voltage | 25 | 35 | 45 | 55 | 66 | |
low frequency Flashover Voltage | Dry-kv | 80 | 110 | 125 | 150 | 175 |
Wet-kv | 60 | 80 | 100 | 125 | 150 | |
Critical Impulse Flashover Voltage | Positive-kv | 130 | 180 | 210 | 255 | 290 |
Negative-kv | 155 | 205 | 260 | 340 | 380 | |
Radio interference voltage | Test voltage to ground-kv | 15 | 22 | 30 | 44 | 44 |
Max RIV at 1000KHz-uv | 100 | 100 | 200 | 200 | 200 | |
Net weight-kg | 5.2 | 9 | 11 | 16 | 18 |